30
Input Register data configuration (3/9)
Word
address
Classification Item name Setting range Contents
00 62
Operation
management
Reserve_1
-
"Reserve" is not initially provided,
but may be added in future.
00 6F Reserve_14
00 70
View alarm
history
Fault/warning message count 0 to 90
Gets the fault/warning message
count.
00 71 Reserve_1
-
"Reserve" is not initially provided,
but may be added in future.
00 73 Reserve_3
00 74 Generation time(year) 2000 to 2099
Gets the generation time of the
message 1.
00 75 Generation time(month) 1 to 12
00 76 Generation time(day) 1 to 31
00 77 Generation time(hour) 0 to 23
00 78 Generation time(minute) 0 to 59
00 79 Generation time(second) 0 to 59
00 7A Fault/warning No. 1 to 999
Gets the fault/warning No. of the
message 1.
00 7B Reserve_1 -
"Reserve" is not initially provided,
but may be added in future.
00 7C
Fault/warning message 2
-
Fault/warning history 02 through
90 are obtained in a same way as
that of Fault warning history 01
(Address: from 0x0074 to
0x007B)
00 83
03 3C
Fault/warning message 90
03 43
03 44
Reserve
Reserve_1
-
"Reserve" is not initially provided,
but may be added in future.
0A FF Reserve_1980
0B 00
Communicati
on
environment
setup
State at power-up 0 to 2
Gets the state at power-up.
0:Comm. port is OFF
1:Comm. port is ON
2:OFF fixed
0B 01 Communication and signal error 0 , 1
Gets the communication and
signal error.
0:Warning, 1:Fault
0B 02 Baud rate(Standard port) 0 to 10
Gets the baud rate of the
standard port.
0:150bps, 1:300bps, 2:600bps
3:1200bps, 4:2400bps
5:4800bps, 6:9600bps
7:19200bps, 8:38400bps
9:57600bps, 10:115200bps
0B 03 Data length(Standard port) 0 , 1
Gets the data length of the
standard port.
0:7 bits, 1:8 bits
0B 04 Parity bit(Standard port) 0 to 2
Gets the parity bit of the standard
port.
0:Disable, 1:Odd, 2:Even
0B 05 Stop bits(Standard port) 0 , 1
Gets the stop bits of the standard
port.
0:1 bit, 1:2 bits
0B 06 Baud rate(Secondary port) 0 to 10
Gets the baud rate of the
secondary port.
0B 07 Data length(Secondary port) 0 , 1
Gets the data length of the
secondary port.
0B 08 Parity bit(Secondary port) 0 to 2
Gets the parity bit of the
secondary port.
0B 09 Stop bits(Secondary port) 0 , 1
Gets the stop bits of the
secondary port.