22
Example Wiring Diagram
The schematic diagram below provides a general example of logic connector wiring, in
addition to basic power and motor wiring converted in the preceding pages. The goal of
this page is to help you determine the proper connections for the various terminals shown
below for your application needs.
Power source,
3-phase or
1-phase, per
inverter model
Relay contacts,
type 1 Form C
Pulse train input
For EzSQ Only.
Brake
resistor
(optional)
RJ45 port
(Optional operator port)
USB (mini-B) port
(PC communication port)
USB power: Self power
Termination resistor (200)
(Change by slide switch)
Serial communication port
(RS485/Modbus)
Intelligent inputs,
7 terminals
NOTE: For the wiring
of intelligent I/O and
analog inputs, be sure
to use twisted pair /
shielded cable. Attach
the shielded wire for
each signal to its
respective common
terminal at the inverter
end only.
Input impedance of
each intelligent input is
4.7k
Jumper wire
(Source logic)
NOTE: Common for
RS485 is “L”.
[5] configurable as
discrete input or
thermistor input