Fine Tuning Functions
Restart mode on
power failure /
under-voltage trip
Select inverter restart method,
Five option codes:
Alarm output after trip, no automatic
restart
Restart at 0Hz
Resume operation after frequency
matching
Resume previous freq. after freq.
matching, then decelerate to stop and
display trip info
Resume operation after active freq.
matching
Allowable
under-voltage
power failure time
The amount of time a power input
under-voltage can occur without tripping the
power failure alarm. Range is 0.3 to 25 sec. If
under-voltage exists longer than this time, the
inverter trips, even if the restart mode is
selected.
Retry wait time
before motor
restart
Time delay after under-voltage condition goes
away, before the inverter runs motor again.
Range is 0.3 to 100 seconds.
Instantaneous
power failure /
under-voltage trip
alarm enable
Three option codes:
Disable
Enable
Disable during stop and decelerates to a
stop
Number of
restarts on power
failure /
under-voltage trip
events
Two option codes:
Restart 16 times
Always restart
Restart frequency
threshold
Restart the motor from 0Hz if the frequency
becomes less than this set value during the
motor is coasting, range is 0.00 to 400 Hz
Restart mode on
over voltage / over
current trip
Select inverter restart method,
Five option codes:
Alarm output after trip, no automatic
restart
Restart at 0Hz
Resume operation after frequency
matching
Resume previous freq. after active freq.
matching, then decelerate to stop and
display trip info
Resume operation after active freq.
matching
Number of retry
on over voltage /
over current trip
Retry wait time on
over voltage / over
current trip