51
Standard Functions
NOTE:. Parameters marked with "" in A column are accessible even in inverter running.
Parameters marked with "" in B column are accessible even in inverter running when in
the high level access mode, which means that b031 is set to "10".
Eight options; select codes:
POT on ext. operator
*Valid when connecting the
OPE-SR/SRmini
Control terminal
*Set to “01” when connecting
the WJ-VL or External volume
via control terminal
Function F001 setting
Modbus network input
Option
via EzSQ
Calculate function output
Frequency source,
2
nd
motor
Four options; select codes:
Control terminal
Run key on keypad, or
digital operator
Modbus network input
Option
Run command source,
2
nd
motor
Settable from 30 Hz to the
maximum frequency()
Base frequency,
2
nd
motor
Settable from 30 Hz to the 2
nd
maximum frequency()
Settable from the base
frequency to 400 Hz
Maximum frequency,
2
nd
motor
Settable from the 2
nd
base
frequency to 400 Hz
Three options; select codes:
...Select between [O] and
[OI] at [AT] (ON=OI,
OFF=O)
...Select between [O] and
external POT at [AT]
(ON=POT, OFF=O)
...Select between [OI] and
external POT at [AT]
(ON=POT, OFF=OI)
[O] input active range
start frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.00 to 400.0 Hz
[O] input active range
end frequency
The output frequency
corresponding to the analog
input range ending point,
range is 0.00 to 400.0 Hz