24
0 to 9.8 VDC range, 10 VDC nominal,
input impedance 10 k
Serial communication terminal
For RS485 Modbus communication.
250VAC, 2.5A (R load) max.
250VAC, 0.2A (I load, P.F.=0.4) max.
100VAC, 10mA min.
30VDC, 3.0A (R load) max.
30VDC, 0.7A (I load, P.F.=0.4) max.
5VDC, 100mA min.
Note 1: The two terminals [L] are electrically connected together inside the inverter.
Note 2: We recommend using [L] logic GND (to the right) for logic input circuits and [L]
analog GND (to the left) for analog I/O circuits.
Note 3: Refer to page 41 for details of trip signals.
Note 4: Refer to page 88, “Functional Safety” for details
Wiring sample of control logic terminal (Source logic)
Note: If relay is connected to intelligent output, install a diode across the relay coil
(reverse-biased) in order to suppress the turn-off spike.
Caution for intelligent terminals setting
Please avoid conducting below procedure, because if you follow procedure describe below, the
inverter setting will be initialized.
1) Turning on power while [Intelligent input terminal 1/2/3 are ON] and [Intelligent input
terminal 4/5/6/7 are OFF].
2) After 1)’s condition, turning off power.
3) After 2)'s condition, turning on power while [Intelligent input terminal 2/3/4 are ON]
and [Intelligent input terminal 1/5/6/7 are OFF].
Variable resistor
for freq. setting
(1k-2k)
Jumper wire
(source logic)