Control Logic Signal Specifications
The control logic connectors are located just behind the front housing cover. The relay
contacts are just to the left of the logic connectors. Connector labeling is shown below.
24VDC, 100mA. (do not short to terminal L)
To change to sink type, remove the jumper
wire between [PLC] and [L], and connect it
between [P24] and [PLC]. In this case,
connecting [L] to [1]~[7] makes each input
ON. Please remove the jumper wire when
using external power supply.
1
2
3/GS1
4/GS2
5/PTC
6
7/EB
Discrete logic inputs
(Terminal [3],[4],[5] and [7]
have dual function. See
following description and
related pages for the details.)
27VDC max. (use PLC or an external supply
referenced to terminal L)
Functionality is based on ISO13849-1 *4
Connect motor thermistor between PTC and
L terminal to detect the motor temperature.
Set in .
2kHz max.
Common is [PLC]
For EzSQ Only.
Common is [L]
Sum of input [1]~[7] currents (return)
Discrete logic outputs [11]
(Terminal [11] has dual
function. See following
description and related pages
for the details.)
50mA max. ON state current,
27 VDC max. OFF state voltage
Common is CM2
In case the EDM is selected, the functionality
is based on ISO13849-1
4VDC max. ON state voltage depression
Discrete logic outputs [12]
50mA max. ON state current,
27 VDC max. OFF state voltage
Common is CM2
100 mA: [11], [12] current return
10VDC 2mA maximum, 32kHz maximum
Sum of [OI], [O], and [H] currents (return)
4 to 19.6 mA range, 20 mA nominal,
input impedance 100