5
Terminal symbols and Screw size
“Use 60/75C Cu wire only” or equivalent.
For models WL200-022S, -004H, -007H, -015H, -022H, -030H, and -040H.
“Use 75C Cu wire only” or equivalent.
For models WL200-002S, -004S, -007S, -015S, -055H, -075H -110H, -150H and -185H.
Inverter Model
Required
Torque (N-m)
Wire range
WL200-002S
WL200-004S
WL200-007S
1.0
AWG16 (1.3mm2)
WL200-015S
1.4
AWG12 (3.3mm2)
WL200-022S
1.4
AWG10 (5.3mm2)
WL200-004H
WL200-007H
WL200-015H
WL200-022H
1.4
AWG16 (1.3mm2)
WL200-030H
1.4
AWG14 (2.1mm2)
WL200-040H
WL200-055H
1.4
AWG12 (3.3mm2)
WL200-075H
WL200-110H
3.0
AWG10 (5.3mm2)
WL200-150H
WL200-185H
3.9 to 5.1
AWG6 (13mm2)