57
A input select for
calculate function
Six options:
Operator
POT on ext. Operator
*Valid when connecting
OPE-SR/SRmini
Terminal [O] input
Terminal [OI] input
RS485
Option
B input select for
calculate function
Calculates a value based on
the A input source (
selects) and B input source
( selects).
Three options:
ADD (A input + B input)
SUB (A input - B input)
MUL (A input * B input)
An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.00 to 400 Hz
Two options:
Plus (adds value to
the output frequency
setting)
Minus (subtracts
value from the output
frequency setting)
Deceleration hold
frequency
Sets the frequency to hold
deceleration, range is 0.00 to
400.0 Hz
Sets the duration of
deceleration hold, range is 0.0
to 60.0 seconds
PID sleep function
action threshold
Sets the threshold for the
action, set range 0.00 to
400.0 Hz
PID sleep function
action delay time
Sets the delay time for the
action, set range 0.0 to 25.5
sec
[VR] input active range
start frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.00 to 400.0 Hz
[VR] input active range
end frequency
The output frequency
corresponding to the current
input range ending point,
range is 0.00 to 400.0 Hz
[VR] input active range
start %
The starting point (offset) for
the current input range,
range is 0. to 100.%
[VR] input active range
end %
The ending point (offset) for
the current input range,
range is 0. to 100 %
[VR] input start
frequency select
Two options; select codes:
Use offset ( value)
Use 0Hz