30
The two diagrams below input wiring circuits using the inverters internal +24V supply.
Each diagram shows the connection for simple switches, or for a field device with
transistor outputs. Note that in the lower diagram, it is necessary to connect terminal [L]
only when using the field device with transistors. Be sure to use the correct connection of
the jumper wire shown for each wiring diagram.
Sinking Inputs, Internal Supply
Jumper wire = [PLC] [P24] position
GND
7
1
Field device
Open collector outputs,
NPN transistors
WL200
P24
1
7
24V
PLC
Input
circuits
+
-
Logic GND
Input common
Jumper wire
Input switches
L
Sourcing Inputs, Internal Supply
Jumper wire = [PLC] [L] position
Common to
[P24]
7
1
Field device
PNP transistor
sourcing outputs
WL200
P24
1
7
24V
PLC
Input
circuits
+
-
Logic GND
Input common
Jumper wire
Input switches
L
GND
to PNP bias
circuits

Table of Contents