54 
DC braking time for 
deceleration 
Sets  the  duration  for  DC 
braking,  range  is  from  0.0  to 
60.0 seconds 
DC braking / edge or 
level detection for [DB] 
input 
Two options; select codes: 
Edge detection 
Level detection 
DC braking force at 
start 
Level of DC braking force at 
start, settable from 0 to 70 % 
Sets  the  duration  for  DC 
braking,  range  is  from  0.0  to 
60.0 seconds 
Carrier frequency 
during DC braking 
Carrier frequency of DC 
braking performance, range is 
from 2.0 to 10.0kHz 
Sets a limit on output 
frequency less than the 
maximum frequency 
(). 
Range is from frequency 
lower limit () to 
maximum frequency 
(). 
0.0 setting is disabled 
>0.0 setting is enabled 
Frequency upper limit, 
2nd motor 
Sets a limit on output 
frequency greater than zero. 
Range is start frequency 
() to frequency upper 
limit () 
0.0 setting is disabled 
>0.0 setting is enabled 
Frequency lower limit, 
2nd motor 
 
 
Jump freq. (center) 1 to 
3 
Up to 3 output frequencies 
can be defined for the output 
to jump past to avoid motor 
resonances (center 
frequency) 
Range is 0.00 to 400.0 Hz 
Jump freq. width 
(hysteresis) 1 to 3 
Defines the distance from the 
center frequency at which the 
jump around occurs 
Range is 0.00 to 10.0 Hz 
Acceleration hold 
frequency 
Sets the frequency to hold 
acceleration, range is 0.0 to 
400.0 
1
Hz 
Sets the duration of 
acceleration hold, range is 0.0 
to 60.0 seconds 
Enables PID function, 
three option codes: 
PID Disable 
PID Enable 
PID Enable with reverse 
output 
Proportional gain has a range 
of 0.00 to 25.00