Network Specific — PROFINET 29 (38)
Attribute 30-series 40-series Change/Action/Comment
#7, Record Data
Mode
See Comment I&M Record data transparent mode (bit 1) is
replaced with the IM_Options command in the
Network PROFINET IO object (0Eh).
If this bit is 0 in the current implementation, no
action is needed
#13, I&M Profile ID Used for all APIs Only used for
“non-zero” APIs
In the 40-series, this attribute is only read for
submodules belonging to a “non-zero” API (e.
g. PROFIdrive profile). Constant values
(F600h, Generic Device and 0004h, Commu-
nication Module) are used for submodules be-
longing to API 0.
In the 30-series this parameter is used for all
API:s.
#14, I&M Profile Spe-
cific Type
Used for all APIs Only used for
“non-zero” APIs
In the 40-series, this attribute is only read for
submodules belonging to a “non-zero API” (e.
g. PROFIdrive profile). Constant values
(F600h, Generic Device and 0004h, Commu-
nication Module) are used for submodules be-
longing to API 0.
In the 30-series this parameter is used for all
API:s.
#15, I&M Version Available Removed Attribute removed in the 40-series. The Any-
bus CompactCom will never request this at-
tribute. The host application cannot influence
the I&M implemented by the Anybus
CompactCom.
16, I&M Supported Available Removed Attribute removed in the 40-series. The Any-
bus CompactCom will never request this at-
tribute. The host application cannot influence
the I&M supported by the Anybus
CompactCom.
#20, Interface
description
Available Removed Attribute removed in the 40-series. The Any-
bus CompactCom will never request this
attribute.
#21, Module ID As-
signment Mode
Available Removed Attribute removed in the 40-series (Incremen-
tal Module Identification removed in the 40-
series). The Anybus CompactCom will never
request this attribute.
#22, System Contact Available Removed Attribute removed in the 40-series. The Any-
bus CompactCom will never request this at-
tribute. System Contact can now only be
reached from the network via SNMP (sysCon-
tact). Also see SNMP MIB-II, p. 33.
#23, PROFIenergy
functionality
Available Removed Attribute removed in the 40-series. The Any-
bus CompactCom will never request this at-
tribute. PROFIenergy is now enabled by the
application having implemented the Energy
Control Object (F0h).