Accenta/Optima Engineer’s Manual
38
Programs (contd)
Immediate (Intruder) Zone
This is a zone which will, when enabled as used and then activated, go into alarm when the panel is set. To
assign a zone as immediate, remove the timed or timed inhibit function and make sure that it is enabled in the
Used Zones section.
4 = Entry Time
This is the time allowed to enter the premises via the entry route and unset the system. The programmable
range is 00-99 seconds. The actual time is multiplied by 10.
00 = 5 seconds
01 = 10 seconds
03 = 30 seconds
99 = 990 seconds (16.5 minutes)
The default is 30 seconds.
LCD Keypad:
While in Engineer program mode, to set the entry time,
• Press to give a choice of programs or press [up arrow] until
P>Programs is displayed then press .
• Select program 1, 2 or 3.
• The first screen to appear is Program Edit Used
Zones.
• Press [4] to enter into Entry Time edit. The Entry
Time can now be changed.
• Enter a [2-digit number] from 00 to 99.
• Press to accept change or to
cancel.
• Press [RESET] twice to leave menu.
LED Keypad:
While in Engineer program mode, to set the entry time,
• Press to give a choice of programs.LED’s 1,
2 and 3 are flashing.
• Select program 1, 2 or 3. If program 1 is selected,
LED 1 is ON.
• Select [4] to enter into Entry Time edit. The Entry
Time can now be changed. LED 1 is ON.
• Enter a [2-digit number] from 00 to 99. LED 1 is
ON.
• Press to accept change or to cancel.
• Press twice to leave menu.
[4]
P>Program Edit
Entry Time? --
P>Select Program
1 2 or 3
P>Program Edit
Used Zones
[Number]
[2-digit number] then or
P>Program Edit
Entry Time
P>Programs
[1]
[4]
12
3
4
5
6
7
8
12
3
4
5
6
7
8
12
3
4
5
6
7
8
[2-digit number]
then or
12
3
4
5
6
7
8
12
3
4
5
6
7
8