EasyManua.ls Logo

Honeywell BC-200 - Detector Sensitivity Settings

Honeywell BC-200
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
BC-200 Manual P/N DOC-01-013 105
9
9
.
.
5
5
.
.
3
3
D
D
E
E
T
T
E
E
C
C
T
T
O
O
R
R
S
S
E
E
N
N
S
S
I
I
T
T
I
I
V
V
I
I
T
T
Y
Y
The control panel provides nine Sensitivity Levels for alarm detection and pre-alarm as follows:
Alarm Sensitivity Levels You can select the sensitivity of a detector from 1 to 9 (1=highest sensitivity; 9=lowest
sensitivity).
Pre-Alarm Sensitivity Levels You can select one of nine levels from 1 to 9 (1=self-optimizing, 2=highest
sensitivity, 9=lowest sensitivity).
You can set the sensitivity levels as fixed or programmed for day and night operation.
Analog Addressable Detectors Sensitivity Settings Table
Detector Type
Alarm
%/Metre Obscuration
Pre
-
Alarm
%/Metre Obscuration
Photo Optical
Level 1 0.50%
Auto
Level 2 2.40% 0.98%
Level 3 3.15% 1.54%
Level 4 3.90% 2.10%
Level 5 4.69% 2.66%
Level 6 5.45% 3.25%
Level 7 6.20% 3.81%
Default
Level 8 6.96% 4.36%
Level 9 7.71% 4.92%
Ionisation
Level 1 1.64%
Auto
Level 2 2.46% 1.31%
Level 3 3.28% 1.64%
Level 4 4.10% 2.46%
Level 5 4.92% 3.28%
Level 6 5.74% 4.10%
Level 7 6.56% 4.92%
Default
Level 8 7.38% 5.74%
Level 9 8.20% 6.56%
Laser (View)
Level 1 0.07%
Auto
Level 2 0.10% 0.07%
Level 3 0.16% 0.16%
Level 4 0.33% 0.33%
Level 5 0.66% 0.66%
Level 6 1.64% 1.64%
Level 7 3.28% 2.30%
Default
Level 8 4.92% 3.28%
Level 9 6.56% 4.92%
Acclimate
Level 1 3.28% Auto
Level 2 3.28% 3.28%
Level 3 3.28 to 6.56% 3.28%
Level 4 6.56% 3.28 to 6.56%
Level 5 6.56 to 13.12% 3.28 to 6.56%
Level 6 6.56 to 13.12% 6.56%
Level 7 6.56 to 13.12% 6.56%
Default
Level 8 13.12% 6.56 - 9.84%
Level 9 63
O
C degrees 6.56 - 9.84%

Table of Contents

Related product manuals