EasyManua.ls Logo

Honeywell BC-200 - Service Menu - Configure; Configure Zones and Points

Honeywell BC-200
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Panel Operation
BC-200 Manual P/N DOC-01-013 58
7
7
.
.
3
3
.
.
5
5
S
S
E
E
R
R
V
V
I
I
C
C
E
E
M
M
E
E
N
N
U
U
C
C
O
O
N
N
F
F
I
I
G
G
This screen allows the operator to choose which point is to be changed / modified.
1) ZONE LIST ZONE GROUPS
2) AZF LIST ALARM ZONES
3) DOUT LIST DIGITAL OUTPUTS
4) DIN LIST DIGITAL INPUTS
5) VIRTUAL LIST VIRTUAL POINTS
6) NETPOINT LIST NETWORK POINTS
7) ANALOG LIST ADDRESSABLE POINTS
8) CHANGE ANALOG ENTER LOOP/DEVICE NUMBER
9) MODULE ADD/REMOVE RING MODULES
28 JAN 1999 14:44:37
SELECT
DOWN
UP
MENU
CONFIGURE MENU
20 JULY 2002 14:44:37
USE UP/DOWN BUTTONS TO SELECT A FUNCTION;
A = 0
F = 0
I = 0
N = 1
DAY MODE
Actions:
Use the UP and DOWN buttons to scroll through
options and then use SELECT to select the
highlighted option (or button 1 to 9 from
numeric keypad)
Press the MENU button to return to the Service
Menu screen.
Selection
Action required
1
Will display the ZONE list as per page 32
Select the ZONE you wish to change then press the Change button to enter the modify sone
screen
2
Will display the AZF list as per page 43
Select the AZF you wish to change then press the Change button to enter the modify point
screen or the Test button to test a point.
3
Will display the Dout list as per page 44
Select the output you wish to change then press the Change button to enter the modify point
screen or the Test button to test a point.
4
Will display the Din list as per page 45
Select the input you wish to change then press the Change button to enter the modify point
screen
5
Will display the Virtual list as per page 46
Select the input you wish to change then press the Change button to enter the modify point
screen
6
Will display the Netpoint list as per page 47
Select the input you wish to change then press the Change button to enter the modify point
screen
7
Will display the Analog addressable loop list as per page 33
Select the loop and device you wish to change then press the Change button to enter the
modify point screen
8
Will prompt for a specific loop and detector / module number and take you directly to the modify
point screen
9
Will PROMPT YOU TO SELECT conventional ring or Analog addressable loop modules and
take you directly to the Add/Remove Module screen.

Table of Contents