Appendix
BC-200 Manual P/N DOC-01-013 109
Actual Fault
Code
Displayed
Possible causes
Beam Blocked FAULT (F024) Beam Detector Fault - Something has come between the detector’s
beam and its reflector.
Alignment Mode FAULT (F025) Beam Detector Fault - A beam detector is in configuration mode.
Device Disabled FAULT (F026) Not used on BC-200.
Zone Disabled FAULT (F027) Not used on BC-200.
Initialisation Mode FAULT (F028) Beam Detector Fault - A beam detector is running through its
initialization sequence.
Incorrect Position FAULT (F029) Beam Detector Fault -
Over Range FAULT (F030) Not used on BC-200 - FMM-4-20.
Under Range FAULT (F031) Not used on BC-200 - FMM-4-20.
Device Inhibit FAULT (F032) Not used on BC-200 - FMM-4-20.
No Threshold
Programmed
FAULT (F033) Not used on BC-200 - FMM-4-20.
Trouble 1 FAULT (F034) Not used on BC-200 - FMM-4-20.
Trouble 2 FAULT (F035) Not used on BC-200 - FMM-4-20.
Comms Loss FAULT (F036) Not used on BC-200 - FMM-4-20.
Command Failed FAULT (F037) Not used on BC-200 - FMM-4-20.
Thermistor Fault FAULT (F038) Not used on BC-200 - FlashScan mode only.
IR Fault FAULT (F039) Not used on BC-200 - FlashScan mode only.
IR Light Saturation FAULT (F040) The infrared sensor on a FSC-851 detector is saturated.
CO 6 Month Of Life FAULT (F041) The CO (carbon monoxide) detection element on a TC840C1000
detector has six months left to expiration.
CO Life Expired FAULT (F042) The CO (carbon monoxide) detection element on a TC840C1000
detector has expired.
CO Fault FAULT (F043) Not used on BC-200 - FlashScan mode only.