EasyManua.ls Logo

Honeywell BC-200 - FIM Output and Expansion Relay Connections

Honeywell BC-200
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
BC-200 Manual P/N DOC-01-013 113
9.6.1.6 MAIN TERMINATION BOARD CONNECTING RELAY OUTPUTS
4 x Clean Contact Relays 4 x Monitored 24V Outputs (4k7 EOL Resistors)
+AZ1
-AZ1
+AZ2
-AZ2
TERMINATION BOARD
+POW A
-PO W A
+POW B
-PO W B
TERM 4
TERM 2
Comms
Terminal
-CO M A
+COM A
-CO M B
+COM B
NO
CM
NC
NO
CM
NC
NO
CM
NC
NO
CM
NC
TERM 5
+
PR3
-
+
PR4
-
TERM 1
+
BELL
-
+
W/SYS
-
NO
CM
NC
NO
CM
NC
NO
CM
NC
NO
CM
NC
TERM 5
9.6.1.7 MAIN TERMINATION BOARD PANEL EXPANSION RELAYS
TERMINATION BOARD
J16 J17
OUT
IN
Note that the panel expansion relay boards must be connected in a closed serial loop between
J16 and J14 on the Main Termination Board for the software to auto-detect the actual number of
Relay boards connected. The maximum allowed is 8 x 8 way relay boards. If the serial loop is left
open, the panel will assume that all 8 boards are present.
Note: If no expansion relay boards are used, jumper pins J18, situated close to the J14 connector,
must be shorted together.

Table of Contents

Related product manuals