9.7.2.3 PRINTER OUTPUT FORMAT
Event(max 18 char) Zone Point Label(max 28 characters) Date Time
--------------------------------------------------------------------------------
Event Format:
:ALARM Z002 1.1.Z2 ROOM 75 ON SECOND FLOOR 03/03 10:07;
:RESET Z002 1.1.Z2 ROOM 75 ON SECOND FLOOR 03/03 10:08;
:ALARM CLEARED Z002 1.1.Z2 ROOM 75 ON SECOND FLOOR 03/03 10:08;
:PREALARM Z999 L4D99 ROOM 15 ON THIRD FLOOR 03/03 10:10;
:PREALARM CLEARED Z999 L4D99 ROOM 15 ON THIRD FLOOR 03/03 10:10;
:FAULT F05 Z000 L1M7 MONITOR MODULE 03/03 10:12;
:FAULT CLEARED Z000 L1M7 MONITOR MODULE 03/03 10:13;
:ACKD ISOL Z000 L1M1 PUMP RUN 03/03 10:14;
:DE-ISOLATE Z000 L1M1 PUMP RUN 03/03 10:17;
:ACTIVE Z000 0.4.O2 WARNING SYSTEM OUTPUT 07/03 14:39;
:ACKD ISOL FAULT Z000 L2D99 KITCHEN IN BUILDING E 07/03 14:39;
System Fault Format:
:SYSTEM Z000 SYSTEM POWER UP 03/03 11:33;
:FAULT Z000 0.2.I6 BATTERY FAULT 03/03 11:33;
:FAULT CLEARED Z000 0.2.I6 BATTERY FAULT 03/03 11:33;
:SYSTEM Z000 SYSTEM NORMAL 03/03 11:33;
:FAULT Z000 0.10.2 PORTA FLT 03/03 11:34;
:FAULT Z000 NODE100. NODE DOWN 03/03 11:46;
:FAULT Z000 0.10.3 PORTB FLT 03/03 11:46;
:FAULT CLEARED Z000 0.10.3 PORTB UP 03/03 11:47;
:FAULT CLEARED Z000 NODE100. NODE UP 03/03 11:47;
:FAULT Z000 N100.0.10.2 PORTA FLT 03/03 11:47;
:FAULT Z000 N100.0.10.3 PORTB FLT 03/03 11:47;
:FAULT CLEARED Z000 N100.0.10.2 PORTA UP 03/03 11:47;
:FAULT CLEARED Z000 N100.0.10.3 PORTB UP 03/03 11:47;
:FAULT CLEARED Z000 0.10.2 PORTA UP 03/03 11:49;
:FAULT Z000 0.2.I3 RING POWER SHORT 03/03 11:51;
:FAULT CLEARED Z000 0.2.I3 RING POWER SHORT 03/03 11:51;
:SYSTEM Z000 0.6.O5 WARN SYS ISOLATED 03/03 10:42;
:SYSTEM Z000 0.6.O5 WARN SYS DE-ISOL 03/03 10:48;
:FAULT Z000 NODE100. NODE DOWN 03/03 10:48;
:FAULT CLEARED Z000 NODE100. NODE UP 03/03 10:49;
:FAULT Z000 N100.0.10.4 PROG MODE ACTIVATED 03/03 10:50;
:FAULT CLEARED Z000 N100.0.10.4 PROG MODE ENDED 03/03 10:50;
Field start positions in output string:
Event First character in each event is a colon ':' followed by max 18 characters for a description
Zone Zone number is max 4 characters long and starts at position 21
Point Point address is max 13 characters long and starts at position 26
Label Label is max 28 characters long and starts at position 40
Date Date is max 5 characters long and starts at position 69
Time Time is max 5 characters long and starts at position 75
There is a semicolon ';' at the end of each line (position 80) followed by a carriage return (ASCII characters 13)
and a line feed (ASCII characters 10)