Panel Operation
BC-200 Manual P/N DOC-01-013 38
7.3.3.7.2.1 Service Menu List List Analog Modules Status
This screen will show a reading of the selected Analog addressable module updated every 3 seconds, 255 times.
The modules current configuration is displayed together with “live readings as shown below.
L1M1 (Z000) > BREAK GLASS ON PANEL
Poll Mode > Flashscan Mode
Programmed As > FMM-101-MMX-101 MINI MON
Actual Device > FMM-101 MINI MON
Device State > NORMAL
Device Status > NORMAL
LED Status > Polling
Device Scanned 255 Times .
ANALOG MENU STATUS
A = 0
F = 0
I = 0
N = 0
20 JULY 2002 14:44:37
DAY MODE
PREV
TEST MenuNEXT RESET
Actions:
Press the PREV buttons to move to the previous
installed point.
Press the NEXT buttons to move to the next
installed point.
Press the TEST button to enter test menu for the
detector.
Press the RESET button to re-initialise the
detector.
Press MENU to return to the Analog Menu
screen.
Explanations of terms:
Variable
Range
Description
Poll Mode CLIP Shows the current polling protocol being used. CLIP = 1
module at a time. Polling mode is auto sensed at start-up
Programmed As 9 Types Module type programmed into panel
Actual Device 5 Types Module type physically seen on loop
Device State Normal/Active/Alarm Shows alarm or activated condition of point
Device Status 23 fault types Detailed description of fault condition. I.e. “No Response”
LED Status 4 Types Polling, On, Off, Polling ID