Panel Operation
BC-200 Manual – P/N DOC-01-013 66
7.3.5.2 SERVICE MENU – CONFIG – MODULE (ADD/ REMOVE)
Overview:
This Config menu is used for adding and removing distributed field modules from the RS485 ring. Even though
the BC-200 auto-detects any new modules and adds them to the system approximately every 5 minutes. You may
have a module that is not physically installed yet, but you wish to configure its inputs etc. You can use this menu
to add the module to the system. If the module is not physically found the panel will register a fault but it will still
allow you to set all the parameters.
Similarly, if a module had been physically removed from the system, you can use this menu item to permanently
remove it from the panel’s memory.
How to Add/Remove modules
MODULES FOUND ON RING 1:
001 002 003 004 005 006 007 101 102 103
NEXTPREV BACK
USE BUTTONS TO SELECT A MODULE:
USE UP/DOWN BUTTONS TO SELECT A RING:
A = 0
F = 0
I = 0
N = 0
ADD REMOVE
DAY MODE
To remove a module:
Use the PREV and NEXT buttons to scroll through
the list of active modules. Once the desired module
is selected, press the REMOVE button once to
remove it.
To Add a module:
Press the ADD button once.
You will be prompted to enter a module number to add.
Then you will be prompted for a module type from the
on screen list of 1-8 i.e. (FANC,AZM8,
ACM16AT,ACM32,SCS8, LDM32, LCD80)
The module has now been added.