Panel Operation
BC-200 Manual – P/N DOC-01-013 79
7.3.7.6 SERVICE MENU – GLOBAL – PRINT
This page displays system global printer port parameters that can be toggled. The default states are shown below
on the left, while the toggled states are shown on the right.
EVENT PRINTING IS DISABLED
ALARM ONLY EVENT PRINTING IS DISABLED
ZONE EVENT PRINTING IS ENABLED
HEARTBEAT CHARACTER PRINTING IS DISABLED
PRINT FORMAT IS SET TO DEFAULT
TOGGLEDOWNUP MENU
SELECT A FUNCTION:
20 JULY 2002 14:44:37
F = 0
I = 0
N = 1
EVENT PRINTING IS ENABLED
ALARM ONLY EVENT PRINTING IS ENABLED
ZONE EVENT PRINTING IS DISABLED
HEARTBEAT CHARACTER PRINTING IS ENABLED
PRINT FORMAT IS SET TO NFS2-3030
TOGGLEDOWNUP MENU
SELECT A FUNCTION:
20 JULY 2002 14:44:37
F = 0
I = 0
N = 1
Actions:
Use the UP and DOWN buttons to scroll through options and then use the TOGGLE button to select the
toggle the highlighted option. Changes are instant.
Explanation of Global Configuration Options:
Item Description
Event Printing
Determines if the panel should print events to the printer port.
Alarm Only Printing
This setting determines if the panel should only print alarm events or all events.
Zone Event Printing
This setting determines if the panel should print zone events as well as single
point events. If this option is enabled, the panel will print two events for a single
alarm condition (zone alarm and point alarm).
Heartbeat Character
Enable this option to print a Carriage Return character every 10 seconds. This
feature can be used to monitor the panel and communications link by a remote
system such as a BMS.
Printing Format
Determines the panel printer port output format. Default setting should be used
unless instructed by Honeywell technicians. The non default format is the same
as the Notifier NFS2-3030 fire panel format and should only be used in
conjunction with the Fieldserver MODBUS gateway. The NFS2-3030 format
does not print all events and should not be used as the standard printing format.