4-97
4. CONFIGURATION
SUB-MATRIX PARAMETER CLASSIFICATION
PERIODIC
REPORT
SYNCHRO AT

DEFINITION:
Synchronization time of first periodic report and following.
HOW TO MODIFY IT:
Enter a new value for time.
POSSIBLE CHOICES:
[0 ... 23] hours
[0 ... 59] minutes
Default value: 00h00
NOTE:
The periodic report will not be printed in "INHIBIT" mode.
The first periodic report will be sent when the nearest time will correspond to
[SYNCHRO AT
& n(PERIOD)] time. (accuracy: 1 second)
"n" is automatically calculated by the recorder so that the synchronization is
effective as fast as possible.
Any configuration modification that stops the acquisitions (with

classification)
or any restart of the recorder will interrupt the current report and will begin a
new one, according to the new parameters.
EXAMPLE:
1) Current time: 13h00
Synchro at: 18h00
Period: 1.50 (1h30)
The first periodic report will be sent at 13h30.
Explanation: 13h30 = 18h00 - 3(1h30)
2) Current date and time: Friday 08/08/1997 at 13h00
Synchro at: 01h00
Period: 168 (1 week)
The first periodic report will be sent on Saturday 09/08/1997, at 01h00.
PE01 SYNCHRO AT
00h00