EasyManua.ls Logo

Honeywell DPR180 - Page 235

Honeywell DPR180
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-21
8. SERVICE
SUB-MATRIX PARAMETER CLASSIFICATION
CURRENT 4/20 mA
CURR CALIB

DEFINITION:
Calibrates the 4 mA and 20 mA references for the selected output.
HOW TO USE/EXECUTE IT:
The "CALIB 4mA" message flashes and the output is supposed to
produce 4 mA. Press the
and keys to start calibration until
reaching the 4 mA output.
In the case where you validated via the ENTER key, the " CALIB 20mA"
message flashes and the output is supposed to produce 20 mA.
Calibration starts when pressing the
and keys until reaching the 20
mA output.
Pressing ENTER makes the calibration stop (the "END CAL" message is
displayed during 3s.)
At any time, SETUP disables the 2 references calibration.
SUB-MATRIX PARAMETER CLASSIFICATION
CURRENT 4/20 mA
VIEW CURR
DEFINITION:
Allows the output current to be displayed under the automatic format.
(from 0 to 24 mA)
HOW TO USE/EXECUTE IT:
Cannot be modified. Press SETUP to escape.
SUB-MATRIX PARAMETER CLASSIFICATION
CURRENT 4/20 mA
FORCE CURR

DEFINITION:
Allows forcing a current output manually on the 0-24 mA range.
HOW TO USE/EXECUTE IT:
Press the and keys to modify the output current.
Press SETUP to escape.
DEFINITION:
[0 ... 24] mA
3 digits after the decimal point
DEFINITION:
0.000

Table of Contents

Other manuals for Honeywell DPR180

Related product manuals