4-13
4. CONFIGURATION
SUB-MATRIX PARAMETER CLASSIFICATION
ANALOG INPUT
EXT COMP
 
DEFINITION:
The thermocouple sensor is directly connected to a remote temperature
compensation box. Then the connections are made with copper lead wires.
Two types of wiring are possible:
1) At a fixed temperature compensation box with temperature configurable
from 0 up to 80
o
C (32 to 176
o
F).
2) On variable temperature compensation box. We use 1 channel to measure
the temperature of the box.
1) Fixed temperature compensation box
2) Variable temperature compensation box
HOW TO MODIFY IT:
1) Fixed Temperature: Enter a new temperature value in engineering
unit. Choose between VALUE 0 and 80.
2) Variable Temperature: Select the channel used to measure the
temperature of the box.
NOTICE
This parameter is just taken into account if the corresponding channel is
configured with T/C EXT COMP. For T/C INT COMP, RTD and LINEAR, this
parameter has no effect whatever the entered value.