4-15
4. CONFIGURATION
SUB-MATRIX PARAMETER CLASSIFICATION
ANALOG INPUT
LOW VALUE

DEFINITION:
Engineering value corresponding to low limit of the selected input
actuation range.
HOW TO MODIFY IT:
Enter a numeric value.
POSSIBLE VALUES:
Up to 4 digits plus optional sign.
[-9999 ... 9999]
NOTICE
Modification is not allowed for any directly connected temperature sensors, as
this would adversely affect the linearization.
Modification is only possible when the sensor is:
- LINEAR or SPECIAL
- RTD and the range is 0, 200 Ohms or 0, 2000 Ohms
NOTICE
For linear and non-linear transmitters choose the value in engineering units,
which corresponds to the low range limit of the transmitter.
SUB-MATRIX PARAMETER CLASSIFICATION
ANALOG INPUT
HIGH VALUE

DEFINITION:
Engineering value corresponding to high limit of the selected input actuation
range.
HOW TO MODIFY IT:
Enter a numeric value.
POSSIBLE VALUES:
Up to 4 digits plus optional sign.
[-9999 ... 9999]
NOTICE
Modification is not allowed for any directly connected temperature sensors, as
this would adversely affect the linearization.
Modification is only possible when the sensor is:
- LINEAR or SPECIAL
- RTD and the range is 0, 200 Ohms or 0, 2000 Ohms
NOTICE
For linear and non-linear transmitters choose the value in engineering units,
which corresponds to the low range limit of the transmitter.