4-36
4. CONFIGURATION
SUB-MATRIX PARAMETER CLASSIFICATION
ALARM
HYSTERESIS
DEFINITION:
Establishes the alarm hysteresis. Alarms switch ON at set point but switch OFF value
depends on the hysteresis setting.
Hysteresis is expressed in Engineering units and is added to low alarm and subtracted from
high alarm set points to establish the alarm release value.
HOW TO
MODIFY:
Enter a numeric value of up to 3 digits, with optional decimal point.
POSSIBLE
VALUES
[0.0 ... 999] (including decimal point)
3 digits after the decimal point available
EXAMPLE:
NOTE:
With CHG rate type, this parameter is expressed in Engineering units.