4-43
4. CONFIGURATION
SUB-MATRIX PARAMETER CLASSIFICATION
ALARM
MSG TYPE
DEFINITION:
Defines when the alarm message is printed.
HOW TO MODIFY IT:
Select a new message type.
POSSIBLE CHOICES:
NONE: The standard message (time, alarm type ...), and the operator
message are not printed.
STD MESSAGE: The standard message (time, alarm type...) is printed at
alarm activation, at alarm release, but operator message is not printed.
MESSAGE ON: Standard operator message is printed at alarm occurrence
only.
MESSAGE OFF: Standard operator message is printed at alarm release only.
MSG ON/OFF: Standard operator message is printed at alarm activation and
at alarm release.
SEE ALSO:
MESSAGE in MESSAGES sub-matrix
NOTE:
The selection of NONE does not prevent the printing of functional messages
such as, messages of range, speed and group change; these are configurable
by the CHART DOC sub-matrix FUNCT MSG parameters.
In case of many MESSAGES the printing order can be changed.