Point Gas Monitor Technical Manual
25
Monitor Operation
• Press enter again to confirm the SetDelay, or use the arrow keys
to select No and cancel the procedure.
Standalone Model Buzzer Menu
The Buzzer menu allows users to select whether or not the built-in audible 
alarm can be silenced by pressing a keypad button and which events will 
activate the buzzer.
* Menu *
Buzzer
• Press enter in the main Buzzer menu screen. The Buzzer screen
displays either Activate or Silence.
• Use the arrow keys to scroll to the desired option and press enter
to select.
Buzzer
Activate
If Silence is selected, the buzzer can be deactivated (without affecting the 
event) by pressing and holding any key on the monitor for 5 seconds.
Select Activate to display available menu options:
B:  The buzzer will activate when alarm level B is reached.
F:  The buzzer will activate upon a system or sensor fault.
Disable:  Buzzer is completely deactivated. However, if there is a 
fault alarm, the buzzer will sound one brief beep once every 
10 minutes.
Standalone Model Alarm Menu
CAUTION: Only qualified, knowledgeable personnel should use the 
programming functions of this monitor. Factory settings conform to specific 
standards (see Specifications). Any changes made to Alarm Levels may 
affect manufacturer’s stated standards compliance.
The Alarm menu allows users to define different alarm levels than the 
factory settings. Press enter to access the Alarm menu options. If there 
is a remote sensor connected, scroll to select either Z1 (built-in sensor) or 
Z2 (remote sensor).
* Menu *
Alarm
Alarm
Z1
• Use the arrow keys to scroll to the Alarm A, B, or C option and