Periphery components for ESSER FACP
18 TI 798960.GB0 / 04.20
Five different texts in different national languages are available as standard for voice announcements e.g.:
In addition, the following languages are available for specific orders. Information refer to the product catalogue.
When the basic setting is selected, signals / signal components can be continuously repeated until the signalling
function is interrupted by the control panel. They can also be programmed with a repetition rate of one to three
times. Thus, the break signal in schools can be deliberately set to only one repetition. In the same way, the total
signal can be set to continuous repetition, with the DIN tone being played only once while subsequent speech
messages are played up to three times.
Programming of the sound level
The sound level [dB (A)] can be programmed from around 64 dB (A) to around 92 dB (A) in eight stages.
All IQ8Quad systems with integrated alarm devices can be operated only on the esserbus
®
PLus.
Since, for physical reasons, a high noise level increases the power consumption of the alarm
device, the respective load factor has to be considered when you are calculating the maximum
number of alarm devices on the loop. In total, it is still possible to operate up to 127 loop devices
per ring bus.
In order to determine the battery capacity of a fire alarm control panel, the
"normally closed @ FACP battery" detector data can be added.
Fire detectors are only to be commissioned, tested and maintained using the control panel software,
version V2.42R006 and higher, and the tools 8000 programming software, V1.05 and higher.
Not suitable for operation on the 8010 extinguishing system and the 8008 FACP!
Separate training is required for planning and commissioning of the IQ8Quad fire detector with
integrated alarm devices.
For additional information and notes, see the product group catalogue.

Table of Contents