Periphery components for ESSER FACP
20 TI 798960.GB0 / 04.20
Part No. Detector type Specific detector specifications
*3
802382
O/So - multisensor
detector with sounder
Quiescent current @ 19 V DC : 80 µA
Quiescent current @ FACP
Accu
: 320 μA
Load factor : 2
Sound pressure level @ DIN tone : 92 dB(A) +/- 2 dB
Sounder specification : EN 54-3:2006
Specification : EN 54-7:2006 /-17:2005
VdS approval : G 206090
Declaration of Performance : DoP-20242130701
802383
O²T/F - multisensor
detector with strobe
Quiescent current @ 19 V DC : 75 µA
Quiescent current @ FACP
Accu
: 400 μA
Load factor : 2
Light intensity of strobe, red : ~ 3 J
Light intensity : max. 15,8 cd peak;
2,63 cd effective
Specification : EN 54-7:2006/-5 B:2000/
-17:2005, CEA 4021
VdS approval : G 205011
Declaration of Performance : DoP-20111130701
802384
O²TSo - multisensor
detector with sounder
Quiescent current @ 19 V DC : 80 µA
Quiescent current @ FACP
Accu
: 450 μA
Load factor : 2
Sound pressure level @ DIN tone : 92 dB(A) +/- 2 dB
Sounder specification : EN 54-3:2006
Specification : EN 54-7:2006/-5 B:2000/
-17:2005, CEA 4021
VdS approval : G 205011
Declaration of Performance : DoP-20192130701
802385 /
802385.SVxx
O²T/FSp - multisensor
detector with strobe,
sounder and voice
output
Quiescent current @ 19 V DC : 90 µA
Quiescent current @ FACP
Accu
: 500 μA
Load factor : 3
Sound pressure level @ DIN tone : -92 dB(A) +/- 2 dB
Light intensity of strobe, red : ~ 3 J
Light intensity : max. 15,8 cd peak;
2,63 cd effective
Sounder specification : EN 54-3:2006
Specification : EN 54-7:2006/-5 B:2000/
-17:2005, CEA 4021
VdS approval : G 205011
Declaration of Performance : DoP-20192130701
802386
O²T/Sp - multisensor
detector with sounder
and voice output
Quiescent current @ 19 V DC : 90 µA
Quiescent current @ FACP
Accu
: 500 μA
Load factor : 3
Sound pressure level @ DIN tone : 92 dB(A) +/- 2 dB
Sounder specification : EN 54-3:2006
Specification : EN 54-7:2006/-5 B:2000/
-17:2005, CEA 4021
VdS approval : G 205011
Declaration of Performance : DoP-20192130701
*3
The information applies for the entire series incl. .MAR, .N0, .NU etc.