10.2.2 IQ8Alarm Plus acoustics without voice
Sound pressure levels for acoustic alarm devices/voice signal devices for exclusive use of acoustics
without voice
Sound pressure level (SPL) [dB(A)]
Tone Description Volume level
Load factor (LF)
Alarm device
Load factor (LF)
Voice signal device
Horizontal angle [°] Vertical angle [°]
15 45 75 90 105 135 165 15 45 75 90 105 135 165
2
Alternating
signal tone,
Frequency
800 Hz/970 Hz
@ 2 Hz
7
3,0
4
78 82 94 96 94 82 78 80 84 93 96 94 81 80
4 77 81 94 96 95 81 77 79 83 93 96 94 80 80
3
1,5
71 76 83 85 84 76 71 72 77 83 85 84 74 72
0 53 57 65 67 65 57 53 54 58 65 67 65 56 54
7
Continuous
signal tone,
Frequency
970 Hz
7
3,0
4
77 82 94 96 94 82 77 79 84 93 96 94 81 80
4 77 82 94 96 94 82 77 79 84 93 96 94 81 80
3
1,5
71 78 81 85 82 78 70 69 80 80 85 81 77 70
0 54 57 63 65 64 57 54 52 56 63 65 63 56 53
10
Alternating
signal tone,
Frequency
1200 ... 500 Hz
@ 1 Hz,
DIN tone in
accordance with
DIN 33404-3
(factory setting)
7
3,0
4
78 83 92 95 92 83 78 78 83 92 95 92 83 78
4 78 83 92 95 92 83 78 78 83 92 95 92 83 78
3
1,5
75 80 88 90 88 80 75 75 79 88 90 88 79 75
0 56 61 69 71 69 62 57 56 61 69 71 69 61 56
11
Alternating
signal tone,
Frequency
554 Hz @
440 Hz
7
3,0
4
75 80 88 89 88 80 75 76 79 88 89 88 79 75
4 75 79 88 89 88 79 75 76 79 88 89 88 79 75
3
1,5
75 79 87 88 87 79 75 75 79 87 88 87 78 75
0 57 61 68 70 68 60 57 57 62 69 70 68 60 57
12
Rising signal
tone,
Frequency
500 Hz ...
1200 Hz
7
3,0
4
80 85 94 96 94 85 80 81 85 94 96 94 83 80
4 78 83 93 95 93 83 78 78 83 93 95 93 81 78
3
1,5
75 80 91 92 91 80 75 76 80 91 92 91 79 75
0 57 62 69 71 69 61 57 57 62 69 71 69 61 57
13
Continuous
signal tone,
Frequency
485 Hz
7
3,0
4
76 76 84 87 84 77 75 76 76 85 87 84 76 75
4 76 76 84 86 84 77 75 76 76 85 86 84 76 75
3
1,5
76 76 83 86 83 77 75 76 76 84 86 84 76 75
0 56 59 65 67 65 59 57 57 58 65 67 65 57 56
14
Cyclic signal
tone,
Frequency
485 Hz
7
3,0
4
76 76 84 86 84 77 75 75 76 84 86 84 76 75
4 76 76 84 86 84 77 75 75 76 84 86 84 76 75
3
1,5
76 76 83 86 83 77 75 75 76 84 86 84 76 75
0 62 63 73 74 73 65 62 62 63 73 74 73 63 62
The table contains the values of minimum sound pressure level and volumes depending on the
direction of emission @ 1 m accordance to EN 54-3 (except 90° angle) in connection with the flat
base.
The values may be up to 0.5 dB lower owing to rounding.
The values for 90° are informative and are not minimum specifications in accordance with EN 54-3.
When using the IP base (806201, 806202) the values can deviate up to -3 dB.