EasyManuals Logo

Honeywell ESSER FACP User Manual

Honeywell ESSER FACP
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
Periphery components for ESSER FACP
TI 798960.GB0 / 04.20 67
10.2.3 IQ8Alarm Plus acoustics and voice
Sound pressure levels for acoustic voice signal devices for simultaneous use of acoustics and voice
Sound pressure level (SPL) [dB(A)]
Tone
Description
Volume
level
Load
factor
(LF)
Horizontal angle [°] Vertical angle [°]
15 45 75 90 105 135 165 15 45 75 90 105 135 165
2
Alternating signal tone,
Frequency 800 Hz/970 Hz @ 2 Hz
7
4
68 72 85 87 85 72 68 70 74 86 87 85 71 71
4 67 71 84 85 84 71 67 69 72 85 85 84 70 70
3 65 70 83 84 83 70 65 67 71 84 84 83 68 69
0 53 57 67 72 66 57 53 55 59 67 72 67 56 56
7
Continuous signal tone,
Frequency 970 Hz
7
4
68 73 86 87 86 73 68 69 74 87 87 87 72 72
4 65 70 84 85 84 70 65 67 72 85 85 84 69 69
3 64 69 83 84 83 69 64 66 71 84 84 83 68 68
0 53 57 65 72 65 57 53 54 58 65 72 66 56 55
10
Alternating signal tone,
Frequency 1200 to 500 Hz @ 1 Hz,
DIN tone in accordance with DIN
33404-3 (factory setting)
7
4
71 76 87 88 87 76 71 72 76 87 88 87 76 71
4 70 75 86 87 86 75 70 71 75 86 87 86 75 71
3 69 75 85 86 85 75 69 70 74 85 86 85 74 70
0 55 60 71 72 71 60 55 56 60 71 72 71 60 56
11
Alternating signal tone,
Frequency 554 Hz @ 440 Hz
7
4
75 80 88 89 88 80 75 76 80 88 89 88 79 75
4 75 79 87 89 87 79 75 75 80 87 89 87 78 75
3 74 78 86 88 86 78 74 74 79 87 88 86 77 74
0 57 62 69 72 69 60 57 58 62 69 72 69 60 57
12
Rising signal tone,
Frequency 500 Hz ... 1200 Hz
7
4
71 76 87 88 87 76 71 72 76 87 88 87 74 71
4 70 75 86 87 86 75 70 71 75 86 87 86 74 70
3 69 74 85 86 85 74 69 70 74 85 86 85 73 69
0 55 60 71 72 71 60 55 56 60 70 72 71 59 56
13
Continuous signal tone,
Frequency 485 Hz
7
4
76 77 84 87 84 77 75 76 77 85 87 84 77 76
4 79 81 84 86 84 81 79 80 81 85 86 84 81 79
3 79 80 83 86 83 80 79 79 80 84 86 84 80 78
0 57 60 65 67 65 59 57 58 59 65 67 65 58 57
14
Cyclic signal tone,
Frequency 485 Hz
7
4
76 77 84 86 84 77 75 76 77 84 86 84 77 76
4 79 80 84 86 84 80 79 79 81 84 86 84 80 79
3 79 80 83 86 83 80 79 79 81 84 86 84 80 78
0 63 65 65 72 65 65 63 63 64 70 72 70 64 62
The table contains the values of minimum sound pressure level and volumes depending on the
direction of emission @ 1 m accordance to EN 54-3 (except 90° angle) in connection with the flat
base.
The values may be up to 0.5 dB lower owing to rounding.
The values for 90° are informative and are not minimum specifications in accordance with EN 54-3.
When using the IP base (806201, 806202) the values can deviate up to -3 dB.

Table of Contents