Page #73 background imageLoading...
Page #73 background image
Periphery components for ESSER FACP
TI 798960.GB0 / 04.20 73
Area of use No.*
tools
8000**
Signal component
Signal description
Duration(s)
11 10
Fire
(France)
French fire sound
Alternating signal tone,
frequency 554 Hz @ / 440 Hz
4,00
12 11
Slow Whoop
(NL)
NL - Slow Whoop
Rising signal tone,
frequency 500 Hz ... 1200 Hz
4,00
13 12 US Horn
US Horn
Continuous signal tone,
frequency 485 Hz
4,00
14 13
US Horn
(Pattern)
US - Horn with Temporal Pattern
Cyclic signal tone,
frequency 485 Hz
4,00
15 14 US March Time
US - March Time
Alternating signal tone,
frequency 485 Hz
4,00
16 15 US Slow Whoop
US - Slow Whoop
Rising signal tone,
frequency 500 Hz ... 1200 Hz
4,50
17 16 US Siren
US - Siren
Rising signal tone,
frequency 600 Hz ... 1200 Hz
4,00
18 17 US Hi/Lo
US - Hi/Lo
Alternating signal tone,
frequency 1000 Hz / 800 Hz
4,00
19 18 US NFPA Whoop
US - NFPA Whoop
Rising signal tone,
frequency 422 Hz ... 775 Hz
3,55
20 19
IMO GA-Signal
(GA-Signal)
Intermittent 800 Hz
(1,0 sec. ON; 1,0 sec. OFF: 7 times;
2.0 sec. ON: 2.0 sec. OFF; Repeat)
18,0
* No. according VdS Certificate
**Signal reference according tools 8000 Software
Other acoustic signals and languages can be combined on a customer-specific basis. The
programming is carried out in the factory. For detailed information, see the product group catalogue.