106 ES-50X Series Manual — P/N LS10129-000FL-E:E  5/23/2022
Programming Maintenance Programming Level
Pressing 2 while viewing Zone Setup screen will display the following screen: 
A flashing cursor appears to the right of the Z. To disable a zone, enter the three digit zone number (000 - 049). After the second digit is 
entered, the zone will be disabled and the cursor will return to the original position. The next zone to be disabled can then be entered. Press 
Esc (Escape) to return to the previous screen.
Pressing 3 while viewing Zone Setup screen will display the following screens: 
Zones 047, 048, 049, and 046 can be programmed for normal zone operation or for special purpose applications. In the above illustration, the 
four zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning them to 
input and output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 47 On. Each press of the 1 key will cause the display to toggle between PAS 47 On and 
PAS 47 Off. When Zone 047 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 047 to 
activate. By assigning Zone 047 to a control module in the Programming Zone Assignment Screen, an output device connected to the control 
module can be used to indicate a PAS condition in the control panel. Do not assign Zone 047 to a Notification Appliance Circuit when using 
this zone to indicate a PAS condition.
Pressing 2 will cause the display to change to Pre-signal 48 On. Each press of the 2 key will cause the display to toggle between Pre-signal 
48 On and Pre-signal 48 Off. When Zone 048 is programmed On, a Pre-signal activation of any device will cause Zone 018 to activate. By 
assigning Zone 048 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can 
be used to indicate a Pre-signal condition in the control panel. Do not assign Zone 048 to a Notification Appliance Circuit when using this 
zone to indicate a Pre-signal condition.
Pressing 3 will cause the display to change to Two Stage 49 On. Each press of the 3 key will cause the display to toggle between Two Stage 
49 On and Two Stage 49 Off. Refer to “Two Stage Operation” on page 79 for a description of this feature. Two-stage operation cannot be 
used at the same time as the in-suite silence feature.
Pressing 1 while viewing the Special Purpose Zone Screen #2 will cause the display to change to Local Alm 46 On. Each press of the 1 key 
will cause the display to toggle between Local Alm 46 On and Local Alm 46 Off. When Zone 046 is programmed On, a Local Alarm activa-
tion of any smoke detector will cause Zone 046 to activate. By assigning Zone 046 to a control module in the Programming Zone Assign-
ment Screen, an output device connected to the control module can be used to indicate a local alarm condition in the control panel. Local 
Alarm Zone alarms are not reported to the Central Station.
  ZONE TO DISABLE
Z444
Disable Screen 
 SPEC PURPOSE ZONE
1=PAS 47         OFF
2=PRE-SIGNAL 48 OFF
3=TWO STAGE 49  OFF
Special Purpose Screen #1
 SPEC PURPOSE ZONE
1=LOCAL ALM 46   OFF
Special Purpose Screen #1