Galaxy 3 Series Programming Manual
D-6
Event Log (cont’d)
NOTE: M = Mandatory. NM = Non-Mandatory
NOTE: A plus (+) means an event has started. A negative (-) means an event has finished.
KEYPAD TEXT DESCRIPTION Trigger Event
RM ACCESS Remote Access zone activated 14. Menu Access NM
+ SEC FINAL Security Final zone activated (opened) 4. Security M
- SEC FINAL Security Final zone closed (closed)
4. Security
18. Zone restoral
M
+ SECURITY Security zone activated (opened). 4. Security M
– SECURITY Security zone de-activated (closed).
4. Security
18. Zone restoral
M
SET LOG Set Log zone activated (opened) when the system or group(s) is set. 16. Log zone M
SOAK TEST Zone under Soak Test (Menu Option 55) activated when the system or group(s) is Set. None NM
SPARE Spare zone opened. 16. Log zone M
STANDLOW Standby time for the battery is Low. 13. Elec status M
SUSP. SET Setting of system suspended None NM
SYS RESET System Reset has occurred event. 11. Reset/Cancel NM
+ TAMP C/V constant Voltage tamper event 9. Tamper M
+ TAMP O/C Zone changing to Tamper Open Circuit (greater than 12,000 Ohm). 9. Tamper M
– TAMP O/C Zone changing from Tamper Open Circuit to Normal Closed (1200 to 900 Ohm).
9. Tamper
18. Zone restoral
M
TAMP RST Tamper Reset of the system has occurred. 9. Tamper NM
+ TAMP S/C Zone changing to Tamper Short Circuit (less than 800 Ohm). 9. Tamper M
– TAMP S/C Zone changing from Tamper Short Circuit (less than 800 Ohm). to Normal Closed (900 to 1200 Ohm).
9. Tamper
18. Zone restoral
M
+ TAMPER
Tamper on a module activated (opened). A module is either a keypad, Galaxy RIO, Telecom Module
or RS232 Module.
9. Tamper M
– TAMPER
Tamper on a module de-activated (closed). A module is either a keypad, Galaxy RIO, Telecom
Module or RS232 Module.
9. Tamper
18. Zone restoral
M
TEST O/P Test Outputs menu (Menu Option 32) has been accessed. None NM
TIMEOUT Timeout alarm after the Entry Time has expired. 10. Setting M
TIMER A + Timer A activated (on). None NM
TIMER A – Timer A de-activated (off). None NM
TIMER B + Timer B activated (on). None NM
TIMER B – Timer B de-activated (off). None NM
T/O-BURGL Timeout alarm after the Entry Time has expired (same as TIMEOUT but used as a SIA event). 2. Intruder M
U/S EARLY The Unset Early output has been activated before programmed time. 10. Setting NM
UNSET Unset of the system or Group(s). 10. Setting M
URGENT Urgent zone activated. 3. 24 Hours M
VIBRATION Vibration zone activated.
2. Intruder
16. Log Zone
NM
VIDEO Video zone activated (opened). 2. Intruder M
VID EXIT Video Exit zone activated (opened). 2. Intruder M
WALK TEST + Walk Test has occurred. 14. Menu access NM
WALK TEST – Walk Test has finished. 14. Menu access NM
WALL TAMP Wall Tamper zone alarm. 9. Tamper M
WRONG CD Wrong Code alarm activation (6 consecutive wrong codes). This Requires a system reset. 9. Tamper M
24 HOURS 24 Hours zone activated (opened). 3. 24 Hours M