Fire Alarm Control Panel IQ8Control C/M
FB 798951.GB0 / 01.09 119
Trouble
Code No.
Possible Cause 1st. measure 2nd. measure
069
There are more detectors on the
loop than programmed in the
customer data.
If this change is not desired,
connect service PC and run
a configuration check. Re-
program customer data.
---
070
Error during detector data
allocation.
If this change is not desired,
connect service PC and run
a configuration check. Re-
program customer data.
---
080
This detector change may only
be performed with the service PC
because this detector required
customer data that cannot be
generated in the panel itself.
If this change is not desired,
connect service PC and run
a configuration check. Re-
program customer data.
---
081
An OTI-detector has been
installed at detector location. The
sensor type has changed in
comparison with the customer
data.
Check whether detector type
change is desired; if it is,
activate analog loop.
Otherwise install detector you
require and re-start >Detector
change<
082
An OT-detector has been
installed at detector location. The
sensor type has changed in
comparison with the customer
data.
Check whether detector type
change is desired; if it is,
activate analog loop.
Otherwise install detector you
require and re-start >Detector
change<
083
An I-detector has been installed
at detector location. The sensor
type has changed in comparison
with the customer data
Check whether detector type
change is desired; if it is,
activate analog loop
Otherwise install detector you
require and re-start >Detector
change<
084
A TM-detector has been installed
at detector location. The detector
type has changed in comparison
with the customer data.
Check whether detector type
change is desired; if it is,
activate analog loop.
Otherwise install detector you
require and re-start >Detector
change<
085
A TME-detector has been
installed at detector location. The
detector type has changed in
comparison with the customer
data.
Check whether detector type
change is desired; if it is,
activate analog loop.
Otherwise install detector you
require and re-start >Detector
change<
086
A TD-detector has been installed
at detector location. The detector
type has changed in comparison
with the customer data.
Check whether detector type
change is desired; if it is,
activate analog loop.
Otherwise install detector you
require and re-start >Detector
change<
087
A O-detector has been installed
at detector location. The detector
type has changed in comparison
with the customer data.
Check whether detector type
change is desired; if it is,
activate analog loop.
Otherwise install detector you
require and re-start >Detector
change<
088
Detector circuitry has been
changed at detector location.
Now detector has neither
external circuit (relay / LED) nor
isolating relay.
If this change is not desired,
connect service PC and run
a configuration check.
Re-program customer data.
---
089
Detector circuitry has been
changed at detector location.
Now detector has external circuit.
(relay / LED).
Check whether this detector
location is to have an
external circuit. isolating
relay. If it is, activate loop.
Otherwise install detector you
require and re-start >Detector
change<
090
Detector circuitry has been
changed at detector location.
Now detector has an isolating
relay.
Check whether this detector
location has an isolating
relay. If it has, activate loop.
Otherwise install detector you
require and re-start >Detector
change<