Fire Alarm Control Panel IQ8Control C/M
120 FB 798951.GB0 / 01.09
Trouble
Code No.
Possible Cause 1st. measure 2nd. measure
091
The IQ8Quad detector circuit has
been changed at the detector
location. Voice output is now also
possible.
Check if the detector type
change is desired; if yes,
reprogram the customer data
and switch on the analog
loop.
Otherwise, install desired
detector and restart
>Detector replacement<
092
The IQ8Quad detector circuit has
been changed at the detector
location. An optical alarm is now
also possible.
Check if the detector type
change is desired; if yes,
reprogram the customer data
and switch on the analog
loop.
Otherwise, install desired
detector and restart
>Detector change<
093
The IQ8Quad detector circuit has
been changed at the detector
location.
Voice output is no longer
possible.
Check if the detector type
change is desired; if yes,
reprogram the customer data
and switch on the analog
loop.
Otherwise, install desired
detector and restart
>Detector change<
094
The IQ8Quad detector circuit has
been changed at the detector
location. An optical alarm is no
longer possible.
Check if the detector type
change is desired; if yes,
reprogram the customer data
and switch on the analog
loop.
Otherwise, install desired
detector and restart
>Detector change<
095
A O
2
T-detector has been
installed at detector location. The
detector type has changed in
comparison with the customer
data.
Check whether detector type
change is desired; if it is,
activate analog loop.
Otherwise install detector
you require and re-start
>Detector change<
096
The IQ8Quad detector circuit has
been changed at the detector
location. An optical and/or
acoustic alarm is no longer
possible.
Check if the detector type
change is desired; if yes,
reprogram the customer data
and switch on the analog
loop.
Otherwise, install desired
detector and restart
>Detector change<
097
The IQ8Quad detector circuit has
been changed at the detector
location. An optical and/or
acoustic alarm is now also
possible.
Check if the detector type
change is desired; if yes,
reprogram the customer data
and switch on the analog
loop.
Otherwise, install desired
detector and restart
>Detector change<
Ionisation smoke detector or fire detector with ionisation sensor may only be opened by authorised
persons with handling license issued under the Radiation Protection Ordinance (German:
Strahlenschutzverordnung - StrlSchV).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell IQ8Control C and is the answer not in the manual?

Honeywell IQ8Control C Specifications

General IconGeneral
BrandHoneywell
ModelIQ8Control C
CategoryControl Panel
LanguageEnglish

Related product manuals