Cabling for Remote Detector/Converter
Honeywell offers the excitation and signal cables as a set under a separate model
number (Model Number KIW-XXX-XXX). Commercially available cables can be
used. The selection of the signal cables depends on certain conditions:
• fluid conductivity,
• length of cable, and
• diameter of the detector.
Figure 9 shows the relation between fluid conductivity and cable length.
3 5 10 20 50 100 200 500 1000
300 984
200 656
100 328
50 164
20 65.6
15 49.2
10 32.8
5 16.4
2 6.6
1 3.3
3 5 10 20 50 100 200 500 1000
300 984
200 656
100 328
50 164
20 65.6
15 49.2
10 32.8
5 16.4
2 6.6
1 3.3
Cable
Length
mft
mft
Cable
Length
Electrical Conductivity (µΩ/cm)
Electrical Conductivity (µΩ/cm)
Detector Sizes: 2.5 and 5mm (0.1 and 0.2 in)
Detector Sizes: 10mm (0.4 in) and greater
The shaded portions are the
areas where commercially
available cables or cables
without shield drives can be
used.
23448
NOTE: Empty pipe detection alarm is available only when the
electrical conductivity of the fluid is greater than 150 µS/cm.
Figure 9—Cable Length Versus Fluid Conductivity