24 www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
Note:  If a MIRO 32/0 is not required in a system, start addressing the 2/16 modules at 
DIP switch 3. If a MIRO 32/0 is configured with an address other than 1 or 2, the 
NetAXS™ panel will not communicate with it. Likewise, if a MIRO 2/16 is 
configured with an address other than 3 through 6, the NetAXS™ panel will not 
communicate with it.
The NetAXS™ board is not intended to provide either module power or module 
output load power for downstream I/O. A separate 24VDC supply should be used to 
provide power to all downstream modules and output loads. For some installations, 
the noise immunity improves if the NetAXS™ common is connected to the 24 VDC 
Return wiring for the downstream modules. This connection is not needed for most 
installations.
Jumper settings JP1 - CLOSED (if the module is 
the last module on the 
downstream bus), OPEN (if the 
module is not the last module on 
the downstream bus)
JP2 - any setting
JP3 - any setting
JP4 - NORMAL
(Positions 1 and 2)
MIRO 2/16 DIP switches Address (switches 1-6) - 3 
through 6
Baud rate (switches 7 and 8) - 7 
= OFF, 8 = ON
OP Mode (switches 9 and 10) - 9 
= OFF, 10 = OFF
Jumper settings JP1 - CLOSED, positions 2 and 
3 (if the module is the last 
module on the downstream bus); 
OPEN, positions 1 and 2 (if the 
module is not the last module on 
the downstream bus)
JP2 - NORMAL, positions 1 
and 2
Table 4  MIRO 32/0 DIP Switch and Jumper Settings (continued)
Module Setting Value