NetAXS™ NX4S1 Installation
System Configuration
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008, Revision A 37
5.11 M-56K Dial-up Modem, RS-485 Connection via NetAXS™
Thirty-one NetAXS™ Access Controller panels for each drop line. It has not been reviewed by UL.
Figure 27: M-56K Dial-up Modem, RS-485 Connection via NetAXS™
COM Port
M-56K
FAX/MODEM
M-56K
FAX/MODEM
Straight Through Cable
NetAXS
Panel
NetAXS
Panel
NetAXS
Panel
EGEG
EGEG
DIP Switch Settings
S1-S5 Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36: OPEN
J37: OPEN
It is recommended to
Earth Ground (EG)
each NetAXS enclosure
Individually
Analog
Phone
Line
Dedicated
analog
phone
line
recommended
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
RS-232 (50 ft.)
RS-485 (4,000 ft.)
See RS-485
Cable Note
DB 9 / DB 25 Connectors
Female Male
1
13
14
25
1
13
14
25
1
5
69
1
5
69
Female 9 Pin Male 25 Pin
(RX) 2 3 (RX)
(TX) 3 2 (TX)
(Comm) 5 7 (Comm)
Male 9 Pin Male 25 Pin
CBL50
RS-485 Cable
NetAXS Panels
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
Terminal