NetAXS™ Standalone Operation
Standalone Commands
NetAXS Access Control Unit NX4L1 Installation Guide, 7-901099, Revision A 57
A.3.6 W (Input) Command
_W=pn_input_{SO|SC|NO|NC}<CR>
Variables:
SO: Supervised normally open
SC: Supervised normally closed
NO: Non-supervised normally open
NC: Non-supervised normally closed (default)
Example:
_W=1_9_SO<CR>
Input 9 has been programmed as supervised, normally open on panel 1.
A.3.7 P (Interlock) Command
_P=pn_I/O_[number]_I/O[number]_{D|E|F|N|P}_
{D|E|F|N|P}<CR>
Parameters:
number: for an input number, the range is 1-96; for output, 0-78
D: De-energize
E: Energize
F: Follow
N: No action
P: Pulse
Example:
_P=1_I_5_O_3_E_D
When Input 5 is triggered, Output 3 energizes.
When Input 5 returns to its normal state, Output 3 de-energizes.