NetAXS™ Standalone Operation
Standalone Settings
A.2 Standalone Settings
A.2.1 NetAXS™ Panel Hardware Settings
Configure the system with an RS-232 connection according to Figure 20 on
page 30.
Set DIP switches 1 through 5 to define the panel number (see Table 3 on
page 22). Panel number 0 is not valid.
Set DIP switch 6 to the OFF position to place the panel into the Multidrop
mode.
Use a personal computers serial communications port (COM1 or COM2) and
a terminal emulation program to configure the NetAXS™ panel for normal
operation.
A.2.2 Communication Settings
Baud Rate: 115200
•Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
A.2.3 Emulation Settings
Echo typed characters locally: YES
Line Delay: 500 milliseconds
A.2.4 Verifying Communications
1. Press the spacebar.
2. Press the carriage return <CR>. “S?” apppear for every online panel and
indicates proper communication between the terminal and panel.