NetAXS™ NX4S1 Installation
System Configuration
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008, Revision A 41
5.15 NetAXS™/NetAXS™ Access Controller Panel Connection Detail
Figure 31: NetAXS™/NetAXS™ Access Controller Panel Connection Detail
12 3
X
DO NOT C ONNECT or
GROUND SHIELD
T o Serial Connection
DIP Switch Settings
S1-S5:Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
DIP Switch Settings
S1-S5:Panel Address
S6: OFF
J36: OPEN
J37: OPEN
DIP Switch Settings
S1-S5:Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
NetAXS TB7
NetAXS TB7
Ground only one
side of cable shield
X
Shield
Ground Shield
485 +
485 -
485
Common
4,000 ft.(1,200 m) max,24 A WG,2 twisted pairs with
shield,120 ohm,23 pf (NCI part no.NCP2441-TN)
12 3
NetAXS Panel
DO NOT
CONNECT
SHIELD
3
1
2
NetAXS TB7