NetAXS™ NX4S1 Installation
System Configuration
5.0 System Configuration
This section provides wiring diagrams for each of the NetAXS™ system configurations.
5.1 RS-485 Connection via PCI-2
This connection supports thirty-one NetAXS™ Access Controller panels for each drop line. It has
been reviewed by Underwriters Laboratories Incorporated (UL). Note that PCI-2 units can also be
wired anywhere along the drop line. See Figure 18 on page 28 and Figure 19 on page 29. Because UL
has reviewed the NetAXS™ panel only as a standalone system, the computer terminal, NetAXS™
gateway panel, and N-485_PCI-2 adapter appear in this section only to illustrate the installation and
programming of the NetAXS™ panel.
Figure 16: RS-485 Connection via PCI-2
COM Port
It is recommended to Ear
NetAXS enclosure
RS-485 Cable
RS485 NetAXS Panels
Red/White
Black/Green
RS-485 COM
TB7-1 (RS485+)
TB7-2 (RS485-)
TB7-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs
shield, 120 ohm, 23 pf (HAS part no. NCP2441-
485
ote
EG
EG
n y ar roun
one side of cable
RS-485 (4,000 Ft.)
RS-232 (50 Ft. Max.)
NetAXS
Panel
EG
DIP Switch Settings
S1-S5 Panel Address
S6: OFF
J36 OPEN
J37 OPEN
Terminal