EasyManua.ls Logo

Honeywell NetAXS NX4S1 - Standalone Commands; T (Time) Command

Honeywell NetAXS NX4S1
73 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NetAXS™ Standalone Operation
Standalone Commands
NetAXS Access Control Unit NX4L1 Installation Guide, 7-901099, Revision A 53
A.3 Standalone Commands
Use the following commands, in the order they are listed, to configure the NetAXS™
panel.
1. T command: Sets the panel’s Time
2. D command: Sets the panel’s Date
3. L command: Creates Time zones for use by the cards
4. C command: Adds or Deletes cards from the panel
5. W command: Program each input for either NO/NC and Supervised or NON
Supervised operation
6. P command: Sets interlocks between input points and/or output points
Note: In all examples, the underbar “_” indicates a “space” character and <CR>
indicates a carriage return.
A.3.1 T (Time) Command
_T=pn_hh:mm<CR>
Variables:
pn = panel number (1-31)
hh = hours (0-23) (Military time)
mm = minutes (00-59)
Example #1:
_T=1_08:30<CR>
This command would set panel 1 to a time of 8:30 AM.
Example #2
_T=6_18:15<CR>
This command would set panel 6 to a time of 6:15 PM.

Table of Contents