EasyManua.ls Logo

Honeywell NOTIFIER AM-8200 - Page 38

Honeywell NOTIFIER AM-8200
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PAGE - 34 Programming Manual AM_8200
NOTIFIER ITALIA Doc. M-162.1-AM8200-ENG Rev A2 AM8200_manu-prog-ENG
At the end of the Auto-programming procedure a summary of the devices found on the line is displayed
Where:
The PROT
(
Protocol
)
control can dis
p
la
y
the table of devices for one of the two
p
ossible
p
rotocols: CLIP or ADV
TYPE = Type of devices found ( see table above)
NEW = N
ew device found
NFO = Devices previously programmed but not coherent with what was detected during the Auto-Learn procedure
TOT
= total of devices detected on the line ( NEW + NFO + correctly programmed devices.)
MIS = Devices previously programmed but not detected during the Auto-Learn
The SAVE control saves the devices detected during the Self-Learn according to the following mode:
- NEW and NFO are initialized through the default data.
- MIS are removed
- The correctly programmed devices keep the current programming
The data relevant to the initialized devices can be subsequently changed by entering the point programming
procedure.
Sample screen for CLIP detectors.
Important Note:
On Each Line, can be installed
a max number of 30 devices using CLIP
protocol.

Table of Contents

Other manuals for Honeywell NOTIFIER AM-8200

Related product manuals