PAGE - 36 Programming Manual AM_8200
NOTIFIER ITALIA Doc. M-162.1-AM8200-ENG Rev A2 AM8200_manu-prog-ENG
Summary of SW Type-ID for modules
INPUT MODULES
CONNECTION TYPE SW Type_ID TYPE OF DEVICE
MON3
Input module
Input module used for N.O. contacts
(Connection in conformity with EN54 rule).
MON
Input module used for N.O. contacts or any device
Not compliant to EN 54
SCON
MMX-2 input module (obsolete module)
Input module used for 4- wire conventional smoke detectors
not detected during the self-programming.
N.B.: this type has a reset time which is longer than the modules
programmed as “MONITOR”
SCO2
It is valid for the M710E-CZ and M710E-CZR module for the connection of
conventional sensors
It is automatically detected during the self-programming
NONA
Input module
Input module used to interface with N.O. contact, with alarm when
It is closed. The activation of a “NONA” type module, does not generate an
Alarm condition, that is:
- the alarm LED is not on
- “APND” or “GPND” type modules do not activate. Only output modules
coupled
to CBE are activated
STAT
Input module used like the NONA device, but each state change is activated
by the buzzer, for one second.
PULL
Same as MON3; in addition, the” MANUAL BUTTON” reading appears
GTW
AGILE WIRELESS GATEWAY NRXI-GATE
NCMN
Input module used to check the N.C. inputs
When the line is off, an alarm is indicated
In case of line short circuit, a FAULTis indicated