PAGE - 72 Programming Manual AM_8200
NOTIFIER ITALIA Doc. M-162.1-AM8200-ENG Rev A2 AM8200_manu-prog-ENG
STR
AddressableStrobewhichfollowsthestatusofthepanelSounder N
TABLE‐3
CallPointsAdvanced CBEY/N
PULL
SameasMON,butlabel“MANUALCallPoint”.”. Y
NONA
InputModuleNonAlarm(nodisplaybutCBEactivation) Y
MACK
InputModuletoACK–SilenceBuzzerfromanimpulsivecontact(KEY) N
MTAC
InputModuletoSILENCEfromanimpulsivecontact(KEY) N
MRES
InputModuletoRESETfromanimpulsivecontact(KEY) N
MTRB
Thecallpointnotpressedgeneratesafaultevent N
NCMN
ThecallpointnotpressedgeneratesanAlarmevent Y
STAT
SameasNONA,butreportanychangeinstatus(ON‐OFF‐ON) Y
TABLE‐4
Sounder/StrobeAdvanced CBEY/N
GSND AddressableSounderthatcanbeSilencedY
SND
AddressableSounderthatfollowsthestatusofthepanelSounder N
GSTR
AddressableStrobethatcanbeSilencedY
STR
AddressableSounderthatfollowsthestatusofthepanelSounder N
GPND
Sounderorstrobeactivatedateachunrecognizedalarm/fault,silenciable. N
APND
Sounderorstrobeactivatedateachunrecognizedalarm,silenciable. N
GAC
Sounderorstrobeactivatedateachalarm N
TPND
Sounderorstrobeactivatedateachunrecognizedfault. N
GTC
Sounderorstrobeactivatedateachfault(latch). N
TRS
Sounderorstrobeactivatedateachfault. N
ZLFT SounderorstrobeactivatedforfaultyDeviceintheZone N
REM Sounderorstrobecontrollableonlybyexternalcommands N
MAINF
SounderorstrobeactivatedforPowerFailure N
ZDIS
Sounderorstrobeactivatedincaseofexclusionofpointorzone. N