ID2000 Series Operating Manual
Appendix 1
A1 - 2997-434-000-4, Issue 4
May 2010
PANEL STATUS: NORMAL
This is the condition of the panel when it is operational,
and there are no uncleared FIREs or FAULTs or PRE-
ALARMs, no part of the system is disabled, and no
TESTing or CONFIGURATION is being carried out. The
LCD displays, indications of the panel and external
equipment are as follows:
LAMP indications: POWER (green) ON
All other LAMPs OFF
The LCD display in Normal Mode is below:
Internal buzzers: OFF
Circuits Controlled Internally: Sounder Circuits: OFF
FIRE, FAULT relays OFF
External Devices:
All CONTROL MODULES should be OFF
- unless operated by an auxiliary action.
The built-in LED indicators on all sensors and modules
should either give short pulses or be off altogether.
The ‘system-normal message’ is a text message specially
customised for your installation, and may consist of an
advertisement, such as the building name, or similar
information.
Note: The MUTE BUZZER, ACCEPT, EVACUATE,
SILENCE SOUNDERS, RESOUND SOUNDERS
and RESET pushbuttons each have an associated
lamp which illuminates when the button is activate,
until superceded by another pushbutton operation.
This is in addition to the indications described in
this Appendix.
PANEL STATUS: EXTINGUISHANT RELEASE
If an Extinguishing System is configured and a release
countdown begins, the LCD will display the following
momentarily on the top line every 4 seconds:
Status: NORMAL (date) (time)
(blank) or (System Normal message)
EXTINGUISHANT RELEASE: nnnsec left