CHAPTER
2
PW-7000 (PW7K1IC) Installation and Configuration Guide, Document 800-25673V1 17
SETTING UP PW-7000 HARDWARE
The PW-7000 processor is configured with 4 jumpers and a set of 4 DIP switches.
These jumpers/switches set up the port interface, end of line termination, and
operating mode configuration. Refer to the tables below to set the jumpers as
required.
Setting the Jumpers
Table 1 PW-7000 Jumper Settings
Setting the DIP Switches
Dual In-line Package (DIP) switches are read when the system powers up, except
where noted otherwise. The following table shows the setting options.
Table 2 PW-7000 DIP Switch Settings
Jumpers Set At Description
J5
OFF RS-485 EOL Terminator is without termination
ON RS-485 EOL Terminator is terminated
J7
Reader Power Select
Reader 0 5V-12V, 2-3 12V (default), 1-2 5V
J8
Reader 1 5V-12V, 2-3 12V (default), 1-2 5V
J19
OFF= Battery OFF ON = Battery ON
S1 S2 S3 S4 Selection
OFF OFF OFF OFF Normal Operating Mode.
ON OFF OFF OFF Enables the default user name (admin) and (password). The user name and
password are read dynamically; you do not need to reboot the panel.
OFF ON OFF OFF Use the factory default communication parameters.