7) Technical Specifications
RAEGuard Lite gas detector
Use
Universal transmitter with standard configuration of 3-wire, 4-20mA and RS485 MODBUS output
for use with a wide range of applications for the detection of flammable, toxic and Oxygen gas
hazards.
Electrical parameters
Input Voltage Range
16-32VDC (24VDC nominal)
Typical Power Consumption
Electrochemical Cells: <1watts; catalytic:2 watts(Max:5w)
Current Output
Completely configurable 4-20mA (source type) with optional HART® 7.2 protocol as following as
default configurations of current output.
1mA Fault 2mA Inhibit (during configuration or setup)
3mA Warning 4mA~20mA Normal
22mA overrange
Note: When the current output is <3mA, HART communication will not work properly.
Terminals
5 terminals (11 terminals for use with relay output), wire diameter 0.5mm
2
20AWGto 2.5mm
2
13AWG
Relays
3 Relays 30VDC 5A,optional)
Communication
RS485, Modbus RTU
Optional Bluetooth /Hart (coming soon)
Construction
Transmitter Housing
Material
Aluminum Alloy
Sensor Housing Material
316 Stainless Steel
Weight (approx.)
Aluminum Alloy: 2.3kg;
Mounting
Integral mounting plate with 4 x mounting holes suitable for M8 to fit onto Wall or Pipe
Entries
2 x 3/4'' NPT cable/conduit entries and 1 x M25 sensor entry. 1 x plug supplied f for only 1 entry
used. Seal to maintain IP rating
Performance****
Repeatability
<2%
Response Time(T90 sec)
Depending on sensor
Certification
China
LEL: Ex db IIC T6 GbEx tb IIIC T80°C Db Ta = -40°C ~ +65°C
Ex db IIC T5 GbEx tb IIIC T90°C Db Ta = -40°C ~ +75°C
EC: Ex db IIC T6 GbEx tb IIIC T80°C Db Ta = -20°C ~ +55°C
EMC
EN50270:2015, IEC 61000-4-5
Surge Immunity
Optional Surge Protection Device, Compliance with GB/T17626.5-2008/IEC61000-4-5:2005,
Meets “Installation Class 4”
Environmental
IP Rating
IP66
Operating Temperature***
-40°C to +70°C
Operating Humidity
LEL: 0~95%RH (Non-condensing)
Toxic & Oxygen: 15%~95%RH (Non-condensing)
Operating Pressure
90~110kPa
Storage Conditions
-20°C to +50°C, 45-75%RH(Non-condensing), in clean air
Remarks:
* RAEGuard Lite will provide users more communication interfaces and gas types in the future, such as wireless etc. For
availability, please contact Honeywell Analytics.
*** Catalytics sensor can work continuously at -40°C ~ +70°C; toxic and Oxygen sensor can work continuously at -20°C ~ +55°C,
intermittently at -40°C ~ +70°C (The accuracy and response time of sensors operating in this temperature range will be affected,
and long-term operation may lead to sensor sensitivity decline or even damage.)
**** The performance characteristics of the products mentioned above are typical results tested in an environment with a
temperature 20°C and a humidity of 50% RH. When calibrating, use the calibration cap and recommended flow for detection. If
the sunshade/deluge is used instead or the detection is carried out at low temperature, the response time will be slowed down.
7